802.3bt Type 4 delivers 90 W at the switch port and roughly 71 W at the powered device. It is the standard behind most "PoE++" claims in tenders today. It is also frequently specified where it is not needed, which raises cost, heat and cable requirements for no benefit.

Here is where Type 4 genuinely earns its place.

Pan-tilt-zoom cameras with heaters and wipers are the classic case. A large outdoor PTZ can draw 25 to 35 W steady, then spike when the heater runs at minus twenty or the wiper motor starts. Type 3 at 60 W covers most of these; Type 4 is justified when the unit also carries a long-range illuminator or a second radio module.

Multi-radio Wi-Fi access points are the second case. A Wi-Fi 6E or Wi-Fi 7 access point with three or four radios, 6 GHz operation and 10 GbE uplink can exceed 40 W under load. Vendors increasingly ship these with 802.3bt requirements, and a 30 W PoE+ port will either refuse to power them or force a reduced-radio mode that customers notice.

PoE lighting is the third. High-brightness luminaires, tunable-white fixtures and lighting controllers with sensors regularly land in the 40 to 70 W range. Lighting circuits also run continuously, so efficiency and thermal design matter more than on a camera circuit that idles at night.

Digital signage and small edge devices are the fourth. Menu boards, information panels and compact edge servers with PoE input are usually specified at Type 4 because their peak draw is unpredictable.

What Type 4 demands from the installation is where projects fail.

Cable first. af and at use two pairs; Type 3 and Type 4 use all four. That means every pair must be terminated and tested, not just the two data pairs. Marginal Cat5e often works on at and fails intermittently on bt: the symptom is a port that powers up, drops after twenty minutes, then renegotiates. Use Cat6 or Cat6A, keep the channel under 100 metres, and treat any splice or cheap patch lead as a defect.

Heat second. Delivering 90 W over four pairs means higher current and higher temperature rise in the bundle, especially in insulated walls or crowded conduit. Plan for it: fewer high-power ports per conduit, space between bundles, and a switch that derates honestly. Ask for the power budget at 50 degrees Celsius, not at 25.

Budget third. A 24-port bt switch with a 400 W budget does not run twenty-four 90 W ports. Divide the total budget by the worst-case device draw to find the real usable port count at full power, then check whether your peak coincides. Camera heaters, wiper motors and AP peak loads often do coincide, because they are all triggered by the same weather or the same busy hour.

Power negotiation fourth. Type 3 and Type 4 introduce classes 5 to 8 and, on many platforms, LLDP-based power negotiation. Mixed fleets of af, at and bt devices on the same switch usually work, since each port negotiates independently, but older PDs that do not implement class negotiation may be allocated conservatively. If a device boots slowly or reports insufficient power, check the class allocation before blaming the cable.

A practical decision rule: specify Type 3 for heated PTZ and multi-radio APs, and Type 4 only when a single device exceeds roughly 50 W at the device, or when you need the full 60 to 71 W envelope with headroom for future firmware. Overspecifying every port to Type 4 costs money on the switch, on the cable and on cooling.

If you are specifying a PoE++ project, send the device list with worst-case wattage and port count. We will return the budget calculation, the recommended type per port group and the cable requirements in writing.